Honeywell Ciper IO Module Overridden @ 1 Or Intermittent Bouncing Between Auto Control and Override

Honeywell Ciper IO Module Overridden @ 1 Or Intermittent Bouncing Between Auto Control and Override

Honeywell Ciper controllers have an issue with the hand off auto switches quality. This causes the switches to intermittently go into override.  When you find an output that shows overriden @ priority 1 in Niagara you can't control it or override it from Niagara.  Even an emergency override won't work.  Sometimes the output will bounce back and forth from auto control to hand or off.  The solution to fix this is to upgrade the firmware in the Honeywell Ciper controller and then disable the hand off auto switches from the software.  See attached Honeywell service bulletin that is attached.